5
2143014.05 06/2014 GB/D
GB
WIKA operating instructions temperature transmitter, model T19
2. Before mounting
2.1 Transmitters with standard measuring ranges
Series T19 transmitters with standard measuring ranges are congurable
by means of solder bridges. Access to the solder bridges is gained after
removing the bottom of the casing. Mounted transmitters have to be
dismantled rst before they can be congured.
To work properly, the transmitter has to be congured. Make
sure that the transmitter is congured before mounting.
Conguration is to be carried out as described in section 3.
As an option standard measuring ranges can be congured at the factory
and in this case the appropriate measuring range is printed on the rating
plate. Transmitters with standard measuring range congured at the
factory can be immediately tted at the measuring point and put into
operation.
2.2 Transmitters with special measuring ranges
Series T19 transmitters with special measuring ranges cannot be
recongured. Special measuring ranges can be recognised by a 9 as last
digit in the model designation: T19.x0-xx0-9
Special measuring ranges are congured at the factory and can be
immediately tted at the measuring point and put into operation.
2. Before mounting
Vue de la page 4