19WIKA operating instructions pressure transmitter model D-1x-7
2478159.05 12/2011 GB/D/F/E
GB
Description of services
Software and hardware version
Via these services it is possible to read the rmware and hardware version.
Start and end of the measuring range
The byte "MBA (value)" or "MBE (value)" contains the amount of the corresponding value, where the
second most signicant bit is taken as the algebraic sign (0=positive, 1=negative). This value is to be
calculated with the measuring range factor:
Date of manufacture
Service byte 1 contains the month of manufacture in the format MM (e.g. 08 for August) and service
byte 2 the year of manufacture in the format YY (e.g. 02 for 2002).
6. Commissioning, operation
Factor / unit (byte 3)
7 6 5 4 3 2 1 0
Exponent
00 00 00 0 ⇒ value x 10
0
00 00 01 1 ⇒ value x 10
1
00 00 10 2 ⇒ value x 10
2
00 00 11 3 ⇒ value x 10
3
Sign of the exponent
0 = positive
1 = negative
Measurement type
0 = relative pressure
1 = absolute pressure