Basic adjustment
Display
Diagnostics
Service
Info
2 Conrm the menu "Basic adjustment" with [OK], the menu item
"Unit" will be displayed.
Unit
Unit of measurement
bar
Temperature unit
°C
3 Activate the selection with [OK] and select "Units of measure-
ment with [->].
4 Activate the sel ection with [OK] and select the requested unit with
[->] (in the example mbar).
5 Conrm with [OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to mbar.
Proceed as follows to select the temperature unit:
7)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
à Conrm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1 Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Oset
P
=
+0000 mbar
53 mbar
2 Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
Accept
Edit
3 Conrm with [OK] and move to min.(zero) adjustment with [->].
7)
Selection options: °C, °F.
Carry out position cor-
rection
30 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor 4 20 mA/HART
6 Set up with the indicating and adjustment module
31543-EN-090130