35
Parameter
Rel.
Index
Description Type Store
Size
byte
RO /
R/W
Min. Max. Default
HI_LIM
51 The setting for high alarm in engineering units. Float SRC 4 R/W
PV_
SCALE
+INF +INF
LO_PRI
52 Priority of the low alarm.
Un-
signed
8
SRC 1 R/W 0 15 0
LO_LIM
53 The setting for the low alarm in engineering units. Float
SRC
4 R/W -INF
PV_
SCALE
-INF
LO_LO_PRI
54 Priority of the low low alarm.
Un-
signed
8
SRC 1 R/W 0 15 0
LO_LO_LIM
55 The setting of the low low alarm in engineering units. Float
SRC
4 R/W -INF
PV_
SCALE
-INF
DV_HI_PRI
56 Priority of the high deviation alarm.
Un-
signed
8
SRC 1 R/W 0 15 0
DV_HI_LIM
57
The setting of the high deviation alarm limit in engineering
units.
Float SRC 4 R/W 0
PV
span
+INF
DV_LO_PRI
58 Priority of the low deviation alarm.
Un-
signed
8
SRC 1 R/W 0 15 0
DV_LO_LIM
59
The setting of the low deviation alarm limit in engineering
units.
Float SRC 4 R/W
-PV
span
0 -INF
HI_HI_ALM
60
The status for high high alarm and its associated time
stamp.
DS-71 D 16 R/W
HI_ALM
61 The status for high alarm and its associated time stamp. DS-71 D 16 R/W
LO_ALM
62 The status of the low alarm and its associated time stamp. DS-71 D 16 R/W
LO_LO_ALM
63
The status of the low low alarm and its associated time
stamp.
DS-71 D 16 R/W
DV_HI_ALM
64
The status and time stamp associated with the high devia
-
tion alarm.
DS-71 D 16 R/W
DV_LO_ALM
65
The status and time stamp associated with the low devia
-
tion alarm.
DS-71 D 16 R/W