WIKA operating instructions temperature transmitter, model T24 17
2370242.09 08/2013 GB/D
If a 2-wire conguration is used:
Set a jumper between the input terminals and . Otherwise the
transmitter will signal a sensor burnout and set the output signal
< 3.6 mA or > 21.0 mA, dependent on conguration.
6.3 Conguration
Sensor type, sensor connection, measuring range, signalling as well
as further parameters can be congured (see data sheet TE 24.01).
The temperature transmitters are delivered with a basic conguration
(Pt100, 3-wire, 0 ... +150 °C, downscale) or congured according to the
customer‘s specications within the given conguration possibilities.
For customer-dened congurations, the input and measuring range
is given on the product label. The initial value of the measuring range
is between -200 ... +200 °C (T24.10.2Px) or between -150 ... +150 °C
(T24.10.1Px). The possible end value of the measuring range is
dependent on the respective initial value of the range. For possible
combinations of initial value of measuring range/end of measuring
range see the diagram on page 19. For the purpose of clarity this
dependency is represented in 50 °C steps in this diagram, though
intermediate values are also congurable. Possible combinations of
the lower and upper limits of the measuring range can be check easily
by the software WIKA_TT. Amendments to conguration should be
noted on the product label with a waterproof bre-tipped pen.
To congure the T24 temperature transmitter, a simulation
of the input value is not required. A sensor simulation is
only required for the functional test.
6. Commissioning, operation