3.2 Analogue Input Blocks (PA Slot 1 & 2) Parameter List, Profibus
Parameter
Rel.
Index
Description Type Store
Size
byte
RO /
R/W
Min. Max. Default
ST_REV
1
Static Revision. Counter incremented with every parameter
configuration change.
Un-
signed
16
N 2 RO 0
TAG_DESC
2 A user-supplied description of the block.
Octet
string
SRC 32 R/W
STRATEGY
3
Grouping of Function Block. The STRATEGY field can be used
to group blocks.
Un-
signed
16
SRC 2 R/W 0
ALERT_KEY
4
Contains the identification number of the plant unit. It helps to
identify the location (plant unit) of an event.
Un-
signed
8
SRC 1 R/W 0
TARGET_MODE
5
Contains desired mode normally set by a control application or
an operator.
Un-
signed
8
SRC 1 R/W -
MODE_BLK
6
Contains the current mode and the permitted and normal
mode of the block.
DS-37 D 3 RO
128,152,
8
ALARM_SUM
7 Contains the current states of the block alarms. DS-42 D 8 RO 0;0;0;0
BATCH
8
Intended to be used in Batch applications in line with
IEC61512 Part 1. Necessary in a distributed fieldbus system to
identify used and available channels, in addition used to iden
-
tify the current batch in case of alerts.
DS-67 SRC 10 R/W 0;0;0;0
OUT
10
Contains the current measurement value in a vendor-specific or
configuration-adjusted engineering unit and the belonging state
in AUTO MODE.
DS-33 D 5
RO
**)
Measured of
the variable
state
PV_SCALE
11
Conversion of the Process Variable into percent using the
high and low scale values. The engineering unit of PV_SCALE
high and low scale values are directly related to the PV_UNIT
of the configured Transducer Block (configured via Channel
parameter). The PV_SCALE high and low scale values follow
the changes of the PV_UNIT of the related Transducer Block
automatically, i.e. a change of the Transducer Block PV_Unit
causes no bump at OUT from AI.
2
*
Float
SRC 8 R/W 100; 0
OUT_SCALE
12
Scale of the Process Variable. Contains the values of the lower
limit and upper limit effective range, the code number of the
engineering unit of Process Variable and the number of digits
on the right hand side of the decimal point.
DS-36 SRC 11 R/W
100; 0;
-; -
LIN_TYPE
13 Type of linearisation.
Un-
signed
8
SRC 1 R/W 0
CHANNEL
14
Reference to the active Transducer Block which provides the
measurement value to the Function Block.
Un-
signed
16
SRC 2 R/W
1 : 281
2 : 283
PV_FTIME
16
Filter time of the Process Variable. Contains the time constant
for the rise time of the FB output up to a value of 63.21%
resulted from a jump on the input (PT1 filter). The engineering
unit of the parameter is second.
Float SRC 4 R/W 0
FSAFE_TYPE
17
Defines the reaction of the device if a fault is detected. The
calculated ACTUAL MODE remains in AUTO.
Un-
signed
8
SRC 1 R/W 1
FSAFE_VALUE
18
Default value for the OUT parameter, if sensor or sensor elec
-
tronic fault is detected. The unit of this parameter is the same
as the OUT unit.
Float SRC 4 R/W -
ALARM_HYS
19 Alarm hysteresis. To avoid triggering of many messages. Float SRC 4 R/W
0,5% of
range
HI_HI_LIM
21 Value for the upper limit of alarms. Float SRC 4 R/W
Max
value
HI_LIM
23 Value for the upper limit of warnings. Float SRC 4 R/W
Max
value
LO_LIM
25 Value for the lower limit of warnings. Float SRC 4 R/W
Min
value
LO_LO_LIM
27 Value for the lower limit of alarms. Float SRC 4 R/W
Min
value
HI_HI_ALM
30 State of the upper limit of alarms. DS-39 D 16 RO 0
HI_ALM
31 State of the upper limit of warnings. DS-39 D 16 RO 0
LO_ALM
32 State of the lower limit of warnings. DS-39 D 16 RO 0
LO_LO_ALM
33 State of the lower limit of alarms. DS-39 D 16 RO 0
SIMULATE
34
For commissioning and test purposes the input value from the
Transducer Block in the Analogue Input Function Block AI-FB
can be modified. This means that the Transducer and AI-FB
will be disconnected.
DS-50 SRC 6 R/W
Disabled
OUT_UNIT_TEXT
35
If a specific unit of OUT parameter is not in the code list the
user has the possibility of writing the specific text in this para-
meter. The unit code is then equal to ”textual unit definition”.
Octet
string
SRC 16 R/W -