32 WIKA operating instructions model T32.xS
Maximum permissible load depending on the supply voltage:
Load diagram
11289130.02
Voltage U
B
in V
Load R
A
in Ω
Ex ia Ex nA/ic
For the power supply, use an energy-limited electrical circuit (EN/UL/
IEC 61010-1, section 8.3) with the following maximum values for the
power supply:
for U
B
= DC 42 V; 5 A
For the external power supply a separate switch is required.
9.2 HART
®
loop display (DIH50, DIH52)
Additional conguration of the temperature transmitter with a HART
®
Loop Display is possible. This is used for the local display of the
current process value. The unit and the congured measuring range
of the transmitter are automatically updated via the HART
®
protocol
in the display. No further change of the HART
®
loop display is
necessary. To do this, the display must be in HART
®
mode.