WIKA operating instructions resistance thermometers and thermocouples, Ex n
GB
8. Electrical connection values
8.1 Electrical data without built-in transmitter or digital display
Power and signal circuit
U
max
= 30 V
I
max
= 9 mA
P
max
= 15 mW
Marking
II 3G Ex nA IIC T1…T6 Gc X
II 3D Ex tc IIIC T440°C …T80°C Dc X
8.2 Electrical data for built-in transmitters or digital displays
Power and signal circuit
U
max
= 40 V
The transmitter used must be certied
and conrmed to EN 60079-15.
I
max
= 150 mA
P
max
= 1,000 mW
Sensor current loop
I
max
= 9 mA
P
max
= 15 mW
Marking
II 3G Ex nA IIC T1…T6 Gc X
II 3D Ex tc IIIC T440°C …T80°C Dc X
The transmitters and digital displays used must have their own certication in accordance
with EN/IEC. The installation conditions and electrical connection values can be seen from the
relevant approvals and must be observed.
9. Maintenance and cleaning
9.1 Maintenance
This thermometer is maintenance-free.
Repairs must only be carried out by the manufacturer.
9.2 Cleaning
CAUTION!
Clean the instrument with a moist cloth.
Electrical connections must not come into contact with moisture.
Wash or clean the dismounted instrument before returning it, in order to protect
personnel and the environment from exposure to residual media.
Residual media in dismounted instruments can result in a risk to persons, the
environment and equipment. Take sucient precautionary measures.
For information on returning the instrument see chapter 11.2 “Return”.