Wika TSD-30 Manuel d'utilisateur Page 11

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 100
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 10
11WIKA operating instructions temperature switch model TSD-30
GB
11613025.02 12/2011 GB/D/F/E
3. Specications
Response time
T05 < 5 s (per DIN EN 60751)
T09 < 10 s (per DIN EN 60751)
Maximum working pressure
150 bar
3.5 Accuracy
Analogue signal
≤ ± 0,5 % of span
Switching output
≤ ± 0.8 % of span
Display
≤ ± 0.8 % of span ± 1 digit
Temperature sensor
± (0.15 K + 0.002 | t |)
| t | is the value of the temperature in °C without consideration of the sign.
The actually achievable accuracy is signicantly determined by the mounting situation (immersion
depth, sensor length, operating conditions). This is especially the case for large temperature gradients
between the environment and the medium.
3.6 Reference conditions
Temperature: 15 ... 25 °C
Atmospheric pressure: 950 ... 1,050 mbar
Humidity: 45 ... 75 % relative
Nominal position: Process connection lower mount
Power supply: DC 24 V
Load: see "Output signal"
Vue de la page 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 99 100

Commentaires sur ces manuels

Pas de commentaire