GB
WIKA operating instructions model TR30
11377551.06 07/2014 GB/D
11
Analogue output
4 ... 20 mA, 2-wire
Measuring error per
DIN EN 60770, 23 °C ±5 K
0.2 % (Transmitter)
3)
Linearisation Linear with temperature per DIN EN 60751
Linearisation error ±0.1 %
4)
Switch-on delay, electrical < 10 ms
Signalling of sensor burnout
Congurable: NAMUR downscale < 3.6 mA
(typically 3 mA)
NAMUR upscale > 21.0 mA (typically 23 mA)
Sensor short-circuit Not congurable, generally NAMUR downscale
< 3.6 mA (typ. 3 mA)
Load R
A
R
A
≤ (U
B
- 9 V) / 0.023 A with R
A
in Ω and U
B
in V
Eect of load ±0.05 % / 100 Ω
Power supply U
B
DC 10 ... 35 V
Max. permissible residual
ripple
10 % at 24 V / maximum 300 Ω Load
Power supply input Protected against reverse polarity
Power supply eect ±0.025 % / V
Electromagnetic compatibility
(EMC)
2004/108/EC, DIN EN 61326 emission
(Group 1, Class B) and immunity (industrial
application)
5)
, and also per NAMUR NE21
Temperature units Congurable °C, °F, K
Info data TAG No., descriptor and message can be stored
in transmitter
Conguration and calibration
data
Permanently stored in EEPROM
Electrical connection
M12 x 1 circular connector, 4-pin
Angular DIN connector Form A for cable with
Ø 6 ... 8 mm, cross section max. 1.5 mm²
Readings in % refer to the measuring span
For a correct determination of the overall measuring error, both sensor and
transmitter measuring deviations have to be considered.
1)
For detailed specications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com.
2)
The temperature transmitter should therefore be protected from temperatures over 85 °C
3)
For measuring spans smaller than 50 K additional 0.1 K
4)
±0.2 % for measuring ranges with a lower limit less than 0 °C
5)
Use resistance thermometers with shielded cable, and ground the shield on at least one end of
the lead, if the cables are longer than 30 m or leave the building.
3. Specications