4. Design and function
4.1 Description
ThetemperaturetransmittermodelT12.x0isusedforconvertinga
resistancevalueoravoltagevalueintoaproportionalcurrentsignal
(4...20mA).
Thusthesensorsarepermanentlymonitoredfortheirfault-free
operation.
Theanaloguesignalistransmittedtoaseries-connectedlogicunit
(e.g.aPLCoraswitchcontact)whereitismonitoredforanydeviation
overamaximumvalueorbelowaminimumvalue.
Forfailuremonitoring,thelogicunitmustbecapableofrecognising
bothHIalarms(adjustablefrom21...23.0mA)andLOalarms
(3.6mA).Theelectricalcomponentsofthetransmitteraremountedin
aplasticcaseandfullyencapsulated.
Thetemperaturetransmittermeetstherequirementsfor:
Explosionprotection(dependingontheversion)
Electromagneticcompatibilityinaccordancewith2004/108/EG
SignallingattheanalogueoutputinaccordancewithNAMUR
recommendationNE43
4.3 Scope of delivery
Cross-checkscopeofdeliverywithdeliverynote.