GB
3211517.0707/2010GB/D
WIKAoperatinginstructionstemperaturetransmitterT12 23
6. Commissioning, operation
WARNING!
Anyexistingconnectionbetweenthepositiveandminus
terminalstoanyevaluationsystemmustbedisconnected
inordertoperformtheconguration.
6.3.2 Connection rail mounting version (T12.30.xxx)
Powersupply
Input
red
Disconnect
black
yellow*
green*
T12.30
PU384
32144338X
FortheT12.30(railmountingversion)thereare2possiblewaysto
connect
■
Using the cable "RJ45-connector / 4 coloured crocodile clips"
Connectioninaccordancewiththediagram(andsimilartothatof
theheadmountingversion).
Theredcrocodileclipmustbeconnectedtothepositiveterminal
ofthetransmitter,whiletheblackcrocodileclipmustbeconnected
othenegativeterminalofthetransmitter.
Thegreenandyellowcrocodileclipsonlyneedtobeconnected
wherethemeasuringsignalshouldbefurthertransmittedtoa
connectedevaluationsystem.